D-Flow Slide needs extra input parameters compared to the Study Case:

  • Ψ5m =  -0.03 for sand layers and Ψ5m =  -0.06 for other layers (used in Global step 1)
  • Ψ5m =  -0.03 (used in Global step 5 and Detailed checks)
  • D50 = 180 μm and D15 = 130 μm for Calais sand
  • D50 = 160 μm and D15 = 110 μm for Compacted sand 
  • Cohesive layers factor = 0.2
  • Migration velocity = 0.0001 mm/year

...

 

Unit

Benchmark

D-FLOW SLIDE

Relative error

Marge

[m]

35

35

0.00%

X coordinate of the observation profile (Xsign)

[m]

-35

-35

0.00%

X coordinate of the liquefaction point (XZV)

[m]

30

30

0.00%

Question 1 1a : Would flow slide lead to damage on levee?

 

Yes

Yes

OK

Question 21b: Criterion on slope protection met (<1:2,5)? 

- 

Question 31c: Artificially underwater installed and non-compacted sandy foreland?

 

No

No

OK

Question 41d: Flow slide possible based on geometry onlyon criterion "steepest slope over 5 m"?

 

Yes

Yes

OK

Question 51e: Is liquefaction possibleFlow slide possible based on average geometry only? -Yes 

Question 6: Are there any sensitive to liquefaction layers present?

 

Yes

Yes

OK

Question 7: Is breaching possible? -Yes 

Result of the Global check

 

Failed

Failed

OK

...