Starting with release 2011.02, a task for the MC_SytemAlerter workflow can be configured to send an alert to the Alarmmodule, developed by Imtech for the IWP system. The alert sending has been implemented as an invocation of the Alarmmodule via a SOAP call (also know as a Webservice call). This page how to describe the FEWS-related part of the implementation.

Currently these tasks can only be scheduled using the "Upload task(s) from file" functionality in the Admin interface. The uploaded XML configuratio should conform to the taskList.xsd schema. For examples see below. The Alarmmodule alert part is defined in the referenced mcSystemAlerter.xsd schema.

Configuration

The following documents play a role in the generation of alerts.

  • ModuleConfigFiels\<secondaryValidation>.xml
    Contains the secondary validation rules that will generate logEventCodes that become visible in the logging when rules are exceeded. The log messages generated are defined in this file as well by means of <logEventCode>. It makes sense to choose sensible logEventCodes, for example all log messages used together with the Alarmmodule might start with "Alert.", see also the next section on this. File name is free to choose, secondaryValidation refers to the xsd that is used.
  • RegionConfigFiles\ all three threshold configuration files. See also the wiki page on this: 09 Thresholds
    • RegionConfigFiles\Thresholds.xml
      Defines the level for each threshold with <levelThreshold>. These thresholds can be used to change colors and the use of Flags in the Displays
    • RegionConfigFiles\TresholdValueSets.xml
      Links timeSeriesSets to <thresholdValueSets>
    • RegionConfigFiles\TresholdWarningLevels.xml
      Can be used to define the overlays and colors used when <thresholdWarningLevels> are exceeded, both up and down..
  • DisplayConfigFiles\<scadaDisplay>.xml
    Defines the scada display in which alerts can be used by means of <shapeComponentBehaviourDefinition>. File name is free to choose, scadaDisplay refers to the xsd that is used.

Logging

The configured secondaryValidation monitors the configured timeSeriesSets and logs an exceedance in the FEWS logging tabel. A log file at an FSS might look like this:

The same log messages can be viewed in the FEWS Admin Interface page, via “System Status”and “View Logs”:

They are displayed in the FEWS OC System Monitor as well:

Event action set-up

These screenshots show the IWP system, where all log messages related to the Alarmmodule start with “IWP.”. This commonality makes it easier to set up the Alarmmodule. In this case, an action has been configured in the Admin Interface that comes into action whenever a log messages starting with “IWP.” is logged. The configuration of this action consists of three parts:

  1. Workflows and FSSs >Event and Action Configuration, see also Admin Interface - Workflows and FSSs - Event and Action Configuration
  2. Workflows and FSSs > Event Action Mapping, see also Admin Interface - Workflows and FSSs - Event Action Mappings
  3. Forecast Tasks > Scheduled Tasks, see also Admin Interface - Forecast Tasks - Scheduled Tasks (from 2009.01)

 

Event and Action configuration

 

Here we set up an Action ID (in this example Alarmmodule.alarm) and link it to an <actionxml> configuration file, see the example below. In this example the logEventCode triggers a workflow with has the tag Alarmmodule.alarm. This action is a one off, meaning it will run only once after triggering, opposed to scheduled tasks that run at a fix schedule. Furthermore, this action can't be triggered more that once every 60 seconds. Please note that the Action ID and tag are the same. This is not required by FEWS, but makes it a lot easier for the operator to follow what's going on. 

<?xml version="1.0" encoding="UTF-8" ?>
<actionxml type="task">
<oneoff>
<cardinaltime interval="60" reference="2004-01-01T00:00:00.000+00:00" />
<tag name="Alarmmodule.alarm" />
  </oneoff>
</actionxml>

Event Action Mappings

Here we link the Action ID to a logEventCode. In this example all log messages starting with IWP.* are linked to the Action ID Alarmmodule.alarm. By using the wildcard symbol *, we don't have to specify each and every single eventCode separately. All log messages starting with IWP. will trigger the action we described in the previous secion.

Scheduled Tasks (fixed alert)

Here we link the workflow MC_SystemAlerter to the Event Action by means of a Tag. In the example below, the workflow has the tag Alarmmodule.alarm, which is the same tag we defined in the eventAction configuration file. Thus, this workflow will be run when a log message starting with IWP.* is generated. Please note that it is essential this scheduled task has the following properties:

  • Status is suspended, or <taskStatus>S</taskStatus>
  • Tag is Alarmmodule.alarm, or <taskTag>Alarmmodule.alarm</taskTag>
  • Interval is One-off task, or <taskSelection><singleTask><time0>2011-08-23T09:05:00.000Z</time0></singleTask></taskSelection>

In the fixed alert scenario, the alert is entered as part of the task properties of the scheduled MC_SystemAlerter task in <alarmDiagLine>. This can be used to send regular or one-off alerts and will probably mostly be used for testing purposes.

 

<?xml version="1.0" encoding="UTF-8"?>
<taskList
    xsi:schemaLocation="http://www.wldelft.nl/fews http://fews.wldelft.nl/schemas/version1.0/taskList.xsd"
    xmlns="http://www.wldelft.nl/fews" xmlns:xsi="http://www.w3.org/2001/XMLSchema-instance">
    <task>
        <taskStatus>S</taskStatus>
		<taskTag>Alarmmodule.alarm</taskTag>
		<runOnFailOver>false</runOnFailOver>
        <taskProperties>
            <description>IWP_0_Alarm</description>
            <workflowId>MC_SystemAlerter</workflowId>
            <taskSelection>
                <singleTask>
                    <time0>2011-08-23T09:05:00.000Z</time0>
                </singleTask>
            </taskSelection>
            <forecastPriority>Normal</forecastPriority>
            <makeForcastCurrent>false</makeForcastCurrent>
            <makeStateCurrent>false</makeStateCurrent>
            <mcSystemAlerter>
				<alerts>
					<alarmModuleAlert>
						<webserviceURL>http://localhost:8989/AlarmModuleManager/webservices/alarmService</webserviceURL>
						<alarmDiagLine code="IWP_0_TEST" description="Test Alert from FEWS" source="MC01" level="1"/>
					</alarmModuleAlert>
				</alerts>
			</mcSystemAlerter>
        </taskProperties>
    </task>
</taskList>

Scheduled Tasks (template alert)

The alert with the template is intended to be used as a suspended task which can be triggered through event-action configurations to trigger a single task, in that case, the log messages triggering the alert will be added to the task, if in the template, the following tags are used:

  • %LOG% will be replaced by the message part of log entry
  • %EVENT_CODE% will be replaced by the event code of the log entry
  • %MC_ID% will be replaced by the MasterController ID creating the alert.
<?xml version="1.0" encoding="UTF-8"?>
<taskList
    xsi:schemaLocation="http://www.wldelft.nl/fews http://fews.wldelft.nl/schemas/version1.0/taskList.xsd"
    xmlns="http://www.wldelft.nl/fews" xmlns:xsi="http://www.w3.org/2001/XMLSchema-instance">
    <task>
        <taskStatus>S</taskStatus>
		<taskTag>Alarmmodule.alarm</taskTag>
		<runOnFailOver>false</runOnFailOver>
        <taskProperties>
            <description>IWP_0_Alarm</description>
            <workflowId>MC_SystemAlerter</workflowId>
            <taskSelection>
                <singleTask>
                    <time0>2011-08-23T09:05:00.000Z</time0>
                </singleTask>
            </taskSelection>
            <forecastPriority>Normal</forecastPriority>
            <makeForcastCurrent>false</makeForcastCurrent>
            <makeStateCurrent>false</makeStateCurrent>
            <mcSystemAlerter>
				<alerts>
					<alarmModuleAlert>
						<webserviceURL>http://localhost:8989/AlarmModuleManager/webservices/alarmService</webserviceURL>
						<alarmDiagTemplateLine code="%EVENT_CODE%" description="%LOG%" source="%MC_ID%" level="1"/>
					</alarmModuleAlert>
				</alerts>
			</mcSystemAlerter>
        </taskProperties>
    </task>
</taskList>